MV Aerial Bundle Cable (ABC) Overhead
11KV 33KV Medium Voltage MV Aerial Bundled Conductor (ABC) XLPE Cables
- Phase Conductor : Circular compacted stranded H68 aluminium to BS2627.
- Conductor Screen : Extruded semi-conductive layer.
- Isolatie : XLPE.
- Isolatie Scherm : Extruded semi-conductive layer.
- metallic Screen(optional) : Copper wire screen or copper tape screen.
- Separator : Semi-conductive swellable tape.
- Buitenschede : HDPE.
- Support Conductor : Galvanized steel wires.
- Snelle monsterverwerking met oplossingen op maat
- Hoogwaardige materialen
- Betaalbare Prijs Opties
- Global Delivery
- Zorg er voor een betere gegevensbescherming voor dat alle uploads veilig zijn
Bespaar gemiddeld minimaal 30%
-
Productbeschrijving
Aerial Bundle Cable : Product Description and Specifications
The Aerial Bundle Cable (ABC) series configures insulated overhead conductors for critical LV and MV distribution. Unlike legacy bare wire, this XLPE-insulated design (utilizing AAAC/1350-H19 aluminum) creates a safety-critical barrier, minimizing maintenance requirements. Application Scope: Ranges from 0,6/1kV service drops/lighting to 33kV primary feeders. Structural Options: Manufactured with either an integrated supporting messenger or self-supporting lay, depending on span engineering requirements.
-
Voordelen
Aerial Bundle Cable : Benefits and Features
Grid Classification: 11kV / 33kV. (Medium Voltage Network).
Suspension Logic: Galvanized Steel Messenger. Provides the structural tensile core for Self-Supporting spans.
Spatial Geometry: Compact Bundled Assembly. Reduces visual footprint and easement width requirements compared to bare wire.
Field Stress Control: Dual Semi-Conductive Screens. Physically enforces radial field uniformity to eliminate partial discharge risks.
Sheath Chemistry: HDPE. Specified for high ESCR (Environmental Stress Crack Resistance) and aging immunity in outdoor weathering.
Specification Of Aerial Bundle Cable
| Cross section [mm²] | No. of wires | Conductor diam. [mm] | Overall Diameter [mm] | Minimum breaking load [kgf] | Approx. weight [kg/km] | Max. DC-resistance at 20°C [Ohm/km] | Ampacity 90°C [A] |
|---|---|---|---|---|---|---|---|
| 35 | 7 | 7.1 | 13.6 | 464 | 190 | 0.868 | 187 |
| 50 | 7 | 8.2 | 14.7 | 663 | 235 | 0.641 | 225 |
| 70 | 19 | 9.7 | 16.2 | 928 | 315 | 0.443 | 282 |
| 95 | 19 | 11.5 | 18 | 1259 | 400 | 0.32 | 345 |
| 120 | 19 | 12.9 | 19.4 | 1591 | 500 | 0.253 | 401 |
| 150 | 19 | 14.2 | 20.7 | 1988 | 580 | 0.206 | 456 |
| 185 | 37 | 16.2 | 22.6 | 2452 | 695 | 0.164 | 525 |
| 240 | 37 | 18.4 | 24.9 | 3182 | 875 | 0.125 | 625 |
| Voltage Rating | Number of cores x nominal cross section [mm^2] | Nominal conductor diameter [mm] | Nominal insulation thickness [mm] | Nominal insulation screen thickness [mm] | Nominal sheath thickness [mm] | AAAC/1120 support conductor size [No/mm] | Nominal overall diameter [mm] | Weight [kg/km] | Continuous current rating Still air [A] | Continuous current rating 1m/s wind [A] | Continuous current rating 2m/s wind [A] |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 6.35/11kV | 3x35 | 6.9 | 3.4 | 0.8 | 1.2 | 7/4.75 | 52.4 | 1370 | 110 | 155 | 185 |
| 6.35/11kV | 3x50 | 8.1 | 3.4 | 0.8 | 1.2 | 7/4.75 | 54.6 | 1530 | 130 | 185 | 225 |
| 6.35/11kV | 3x70 | 9.7 | 3.4 | 0.8 | 1.2 | 7/4.75 | 57.8 | 1790 | 160 | 235 | 280 |
| 6.35/11kV | 3x95 | 11.4 | 3.4 | 0.8 | 1.2 | 7/4.75 | 61.3 | 2100 | 195 | 285 | 345 |
| 6.35/11kV | 3x120 | 12.8 | 3.4 | 0.8 | 1.2 | 19/3.50 | 67.3 | 2540 | 230 | 335 | 405 |
| 6.35/11kV | 3x150 | 14.2 | 3.4 | 0.8 | 1.2 | 19/3.50 | 70.1 | 2840 | 255 | 380 | 460 |
| 6.35/11kV | 3x185 | 15.7 | 3.4 | 0.8 | 1.2 | 19/3.50 | 73.1 | 3190 | 295 | 440 | 530 |
| 12.7/22kV | 3x35 | 6.9 | 5.5 | 0.8 | 1.2 | 7/4.75 | 61 | 1780 | 110 | 155 | 180 |
| 12.7/22kV | 3x50 | 8.1 | 5.5 | 0.8 | 1.2 | 7/4.75 | 63.3 | 1970 | 130 | 185 | 220 |
| 12.7/22kV | 3x70 | 9.7 | 5.5 | 0.8 | 1.2 | 7/4.75 | 66.5 | 2260 | 160 | 230 | 275 |
| 12.7/22kV | 3x95 | 11.4 | 5.5 | 0.8 | 1.2 | 7/4.75 | 69.9 | 2600 | 195 | 285 | 335 |
| 12.7/22kV | 3x120 | 12.8 | 5.5 | 0.8 | 1.2 | 19/3.50 | 75.9 | 3070 | 225 | 330 | 395 |
| 12.7/22kV | 3x150 | 14.2 | 5.5 | 0.8 | 1.2 | 19/3.50 | 78.7 | 3390 | 255 | 375 | 450 |
| 12.7/22kV | 3x185 | 15.7 | 5.5 | 0.8 | 1.2 | 19/3.50 | 81.7 | 3760 | 290 | 435 | 520 |
-
Production Processes Of Aerial Bundle Cable
De luchtkabel productie-infrastructuur werkt een gesloten-lus digitale automatisering systeem, integratie van geleider stranding, isolatie extrusie, en uiteindelijke omhulling in een continue workflow Processtabiliteit is afhankelijk van ingebedde sensorarrays volgen extrusie parameters in real-time, het elimineren van handmatige varianties Kwaliteit validatie wordt afgedwongen door middel van specifieke in-line hardware, waaronder dual-axis laserdiameter meters en hoogspanning vonktesters, terwijl het fysieke laboratorium voert destructieve trek - en rekanalyse om naleving van internationale normen te controleren vóór verzending.
Verpakking voor verzending
Om aan verschillende transportbehoeften te voldoen, zijn er veel verpakkingsmethoden die kunnen worden gebruikt.
Heb je nog meer vragen?
Q: Voltage Classification?
A: MV Class. Rated specifically for 11kV en 33kV networks.
Q: Phase Conductor Material?
A: H68 Aluminum. (Circular Compacted Stranded). Naleving: BS2627 Standard.
Q: Suspension Mechanism?
A: Galvanized Steel Messenger. Acts as the primary catenary wire to carry static cable load and tension.
Q: Metallic Screen Options?
A: Configurable. Available with Copper Wire of Copper Tape screens based on fault current specifications. (Default: Optional).
Q: Sheath Composition?
A: HDPE. Selected for high mechanical impact strength and environmental weathering immunity.
Q: Bundle Geometry?
A: Triplex Arrangement. Three screened XLPE cores twisted around the steel messenger (Right-Hand Lay).
Q: Insulation System?
A: XLPE. Thermal Class: 90°C. Provides superior thermal overload retention compared to PVC/PE.