N2XY/NA2XY
0.6/1kV XLPE Insulation and PVC Jacket power cable
- Conductor:Copper / Aluminum , solid or stranded
- Insulation: XLPE
- core color code acc. to VDE 0293
- cores stranded concentrically
- inner covering
- outer sheath, PVC, black
- Procesamiento rápido de muestras con soluciones personalizadas
- Materiales de alta calidad
- Opciones de precios asequibles
- Entrega global
- Para una mejor protección de datos, asegúrese de que todas las cargas sean seguras
Ahorre al menos 30% en promedio
-
Descripción del producto
N2XY/NA2XY : Product Description and Specifications
El N2XY series is your go-to solution for 0,6/1kV industrial and urban grids. Unlike older cables, it uses aislamiento XLPE, which gives you much better thermal stability than standard PVC. You have two options based on budget: N2XY (Copper) for max conductivity, or NA2XY (Aluminum) for cost savings. It comes with a UV-resistant black sheath, making it perfect for fixed installations—just make sure it’s not exposed to heavy mechanical impact since it’s unarmored.
-
Ventajas
N2XY/NA2XY : Benefits & Features
Cobre o Aluminio: Your choice. We stock Cobre (Solid/Stranded) for standard high-conductivity needs, but we also offer Aluminio if you need to slash weight and budget on long distribution runs.
Why XLPE Matters: Usamos Cross-linked Polyethylene (XLPE) instead of basic PVC. This boosts the thermal rating to 90°C, giving you higher ampacity and better overload protection.
Real-World Protection: The outer PVC sheath isn’t just “durable”—it’s formulated to resist UV and abrasion. It holds up fine in trenches (sand bed) or open trays.
No Guesswork: We strictly follow VDE 0293 color coding. Your electricians will know exactly which core is phase, neutral, or earth without needing to ring it out.
Specification Of N2XY/NA2XY
| Technical Data Parameter | Technical Data Value |
|---|---|
| Conductor resistance at 20℃: | según VDE 0295 e IEC 60228 |
| Temperatura centrală, max: | 90℃ in operation |
| Max. short circuit temperature: | 250℃ , not more than 5 sec |
| Rated voltage U0 /U(Umax): | 0,6/1(1,2) kV |
| Voltaje de prueba: | AC ¨C 4 kV (3.5kV by IEC); 50 Hz |
| Temperature range: | |
| flexing: | -5°C la +50°C |
| stationary: | -30℃ to +90℃ |
| Radio de curvatura, mín. | |
| for single-core: | 15xDcable |
| for multi-core: | 12xDcable |
| Specific insulation resistance at 90℃: | min, 1014Ωx cm |
| Max. permissible tensile stress with cable grip: | For Cu conducor = 50 N/mm2 For Al conducor = 30 N/mm2 |
| Cable Structure Component | Cable Structure Description |
| Director: | solid or multi-strand Cu or Al wires class 1, 2 or (5) acc. VDE 0295 (IEC 60228) |
| Aislamiento: | XLPE type DIX3 acc. to VDE 0276-603/5G |
| Identificación central: | según VDE 0293 (HD 308) |
| Signal-command copper core: | Additional, cross section 2,5mm2, red coloured (black coloured 1,5mm2 on request) |
| Cores assembly: | núcleos trenzados concéntricamente (núcleos trenzados en capas concéntricas, para señal) |
| Wrapping: | paper tape |
| Inner covering: | rubber filling compound |
| Vaina: | PVC type DMV6 acc. to VDE 0276-603/sec.1 or PE HDPE mass, type DMP2 acc. DIN VDE 0276/HD603 |
| Color of sheath: | black |
Dimensiones/Parámetros
| Number of cores x Nominal Cross Section | Overall Diameter (Approx.) (mm) | Copper (or Al) Weight (Approx.) (kg/km) | Total Weight (Approx.) (kg/km) |
|---|---|---|---|
| 1x4 | 6.5 | 38 | 74 |
| 1x6 | 7 | 58 | 95 |
| 1x10 | 8 | 96 | 142 |
| 1x16 | 9 | 154 | 205 |
| 1x25 | 11 | 240 | 302 |
| 1x35 | 12 | 336 | 400 |
| 1x50 | 13 | 480 | 526 |
| 1x70 | 15 | 672 | 750 |
| 1x95 | 17 | 912 | 1000 |
| 1x120 | 18.5 | 1152 | 1240 |
| 1x150 | 21 | 1440 | 1550 |
| 1x185 | 23 | 1776 | 1890 |
| 1x240 | 26 | 2304 | 2420 |
| 1x300 | 28 | 2880 | 3015 |
| 2x1.5 | 10 | 42 | 142 |
| 2x2.5 | 11 | 72 | 182 |
| 2x4 | 12 | 115 | 242 |
| 2x6 | 13 | 173 | 320 |
| 2x10 | 15 | 288 | 480 |
| 2x16 | 17 | 461 | 700 |
| 3x25/16 | 21 | 874 | 1220 |
| 3x35/16 | 23 | 1162 | 1450 |
| 3x50/25 | 26 | 1680 | 1955 |
| 3x70/35 | 29 | 2352 | 2720 |
| 3x95/50 | 33 | 3216 | 3750 |
| 4x1.5 | 11 | 58 | 165 |
| 4x2.5 | 12 | 96 | 216 |
| 4x4 | 13 | 154 | 290 |
| 4x6 | 14 | 230 | 385 |
| 4x10 | 16 | 384 | 590 |
| 4x16 | 19 | 614 | 864 |
| 4x25 | 23 | 960 | 1295 |
| 4x35 | 27 | 1344 | 1750 |
| 4x50 | 30 | 1920 | 2300 |
| 4x70 | 34 | 2688 | 3280 |
| 4x95 | 38 | 3648 | 4300 |
| 4x120 | 43 | 4608 | 5416 |
| 4x150 | 47 | 5760 | 6700 |
| 4x185 | 52 | 7104 | 8200 |
| 4x240 | 58 | 9216 | 10560 |
| 5x1.5 | 12 | 72 | 193 |
| 5x2.5 | 13.5 | 120 | 252 |
| 5x4 | 14 | 192 | 340 |
| 5x6 | 15 | 288 | 460 |
| 5x10 | 18 | 480 | 840 |
| 5x16 | 21 | 768 | 1040 |
| 5x25 | 25 | 1200 | 1550 |
| Construction data: NA2XY 0.6/1 kV | |||
| 4x16+1.5 | 21 | 196 | 598 |
| 4x25+1.5 | 24 | 298 | 828 |
| 4x35+1.5 | 27 | 406 | 1022 |
| 4x50+1.5 | 30 | 598 | 1127 |
| 4x70+1.5 | 35 | 812 | 1590 |
| 4x95+1.5 | 39 | 1102 | 1946 |
| 4x120+1.5 | 42 | 1392 | 2436 |
| 4x150+1.5 | 47 | 1740 | 2972 |
| 4x185+1.5 | 52 | 2146 | 3592 |
| 4x240+1.5 | 58 | 2784 | 4572 |
| 4x16 | 21 | 196 | 570 |
| 4x25 | 24 | 298 | 794 |
| 4x35 | 27 | 406 | 974 |
| 4x50 | 30 | 598 | 1110 |
| 4x70 | 35 | 812 | 1510 |
| 4x95 | 39 | 1102 | 1920 |
| 4x120 | 43 | 1392 | 2410 |
| 4x150 | 47 | 1740 | 2946 |
| 4x185 | 52 | 2146 | 3565 |
| 4x240 | 58 | 2784 | 4565 |
-
Procesos de producción de cables de alimentación
Para garantizar una calidad superior, JOCA opera líneas de producción totalmente digitalizadas y automatizadas para cables de alimentación. Específicamente, este flujo de trabajo integral cubiertas trenzado de conductores, extrusión aislante, cribado metálico y revestimiento final. Además, sistem intelligent monitorear activamente cada etapa para garantizar un rendimiento estable y una calidad constante del producto. Además, la fábrica utiliza instalaciones de prueba avanzadas, como pruebas de descarga parcial, pruebas de tracción y pruebas de chispas. En consecuencia, estas medidas rigurosas garantía que cada cable entregado cumpla estrictamente con los estándares internacionales.
Embalaje para envío
Para satisfacer diversas necesidades de transporte, existen muchos métodos de embalaje que se pueden utilizar.
¿Tienes más preguntas?
Q: N2XY vs. NA2XY: What's the actual difference?
A: It’s just the metal inside. N2XY es cobre. NA2XY (with the ‘A’) is Aluminum. That’s it. Since Aluminum is way cheaper and lighter, NA2XY is the smart pick if you have a long run and a tight budget.
Q: Why buy N2XY instead of the cheaper NYY?
A: Simple: Heat. NYY is PVC, so it quits working at 70°C. N2XY uses XLPE insulation, which handles 90°C easily. That 20-degree gap is huge—it lets you push a lot more current (amps) through the same cable without burning it out.
P: ¿Para qué voltaje es esto?
A: Standard Low Voltage grids. 0,6/1 kV.
Q: Can I put this outdoors?
A: Sí. The black sheath handles UV fine. You can run it on trays or even bury it (in sand). Just be careful—it has no armor, so don’t put it where a shovel or rock might smash it.
Q: Temperature limits?
A: 90°C all day long. If there’s a short circuit, it can survive 250°C for a few seconds. PVC cables would basically melt at those temps.
Q: Is the wire solid or stranded?
A: Depends on the size. Small wires (under 10mm²) are usually Solid and stiff. Big cables (16mm² and up) are Varado so you can actually bend them during installation.
Q: Can I get a sample?
A: Sure. We can ship a short piece so you can check the copper quality yourself before ordering a full drum.
P: ¿Cómo obtengo un precio?
A: Simplemente envíenos un correo electrónico BOM (Bill of Materials). Tell us the sizes and total length. We’ll calculate the metal price and send you a quote.