600 volt secondary Type URD cable -aluminum conductor
Single Duplex Triplex and Quaplex Cables for secondary power distribution
건설:
Conductors: Class B compressed stranded Aluminum (1350-H19 or AA-8000 series) per ASTM B231/B800/B801.
절연: Black Thermoset Cross-linked Polyethylene (XLPE).
Applicable Standards:
ICEA S-105-692: 600V Single layer thermoset insulated utility underground distribution cable.
UL 854: Service Entrance Cables.
- 맞춤형 솔루션을 통한 빠른 샘플 처리
- 고품질 재료
- 저렴한 가격 옵션
- 글로벌 배송
- 더 나은 데이터 보호를 위해 모든 업로드가 안전한지 확인하십시오
평균적으로 최소 30% 저장
-
제품 설명
Secondary URD Cable: Product Description and Specifications
Engineered for 600V underground residential distribution, this Secondary URD specification utilizes concentric stranded or compressed 1350-H19 aluminum conductors. The assembly relies on a ruggedized XLPE dielectric system, selected explicitly to block moisture ingress and resist trench abrasion during direct burial or duct installation. Compliance is strictly validated against ICEA and ASTM standards for secondary network reliability, ensuring mechanical durability without requiring additional conduit protection.
-
장점
Secondary URD Cable: Benefits and Features
Dielectric System: Black XLPE. Specified for high thermal stability and abrasion resistance. (No jacket required).
Duct Optimization: Compressed Stranding. Reduces outer diameter (OD). Engineering result: Lowers friction coefficient during duct pulling.
Neutral Identification: Visual Coding: Yellow Striping (or jacket) on neutral. Eliminates phasing errors during termination.
Metallurgy: AA-8000 Series Alloy. Selected for high conductivity-to-weight ratio and superior bend radius compared to standard 1350 aluminum.
Deployment Rating: 600V. Verified for 직접 매장 또는 Raceway (Conduit) installation.
Specification Of Secondary URD Cable
| 유형 | 코드 이름 | Phase Size (AWG/kcmil) | Phase Stranding | Phase Insulation (mils) | Neutral Size (AWG/kcmil) | Neutral Stranding | Neutral Insulation (mils) | Single Phase Diameter (mils) | Complete Cable Diameter (mils) | Weight (lb/kft) | Ampacity Direct Burial | Ampacity Duct/Conduit | NEC Ampacity 60°C | NEC Ampacity 75°C | NEC Ampacity 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Single | Cornell | 8 | 7 | 60 | 260 | 260 | 34 | 74 | 36 | 40 | 44 | 49 | |||
| Single | Princeton | 6 | 7 | 60 | 300 | 300 | 47 | 96 | 47 | 46 | 56 | 59 | |||
| Single | Mercer | 4 | 7 | 60 | 350 | 350 | 67 | 117 | 60 | 63 | 72 | 81 | |||
| Single | Clemson | 2 | 7 | 60 | 410 | 410 | 97 | 154 | 82 | 86 | 100 | 108 | |||
| Single | Kenyon | 1 | 19 | 80 | 490 | 490 | 128 | 171 | 97 | 98 | 111 | 124 | |||
| Single | Harvard | 1/0 | 19 | 80 | 520 | 520 | 154 | 193 | 112 | 115 | 133 | 146 | |||
| Single | Yale | 2/0 | 19 | 80 | 570 | 570 | 186 | 221 | 132 | 132 | 150 | 162 | |||
| Single | Tufts | 3/0 | 19 | 80 | 620 | 620 | 225 | 253 | 155 | 150 | 172 | 189 | |||
| Single | Beloit | 4/0 | 19 | 80 | 680 | 680 | 274 | 290 | 185 | 173 | 200 | 221 | |||
| Single | Hofstra | 250 | 37 | 95 | 750 | 750 | 329 | 317 | 199 | 196 | 228 | 248 | |||
| Single | Gonzaga | 300 | 37 | 95 | 810 | 810 | 385 | 349 | 223 | 224 | 255 | 281 | |||
| Single | Rutgers | 350 | 37 | 95 | 850 | 850 | 439 | 381 | 248 | 242 | 278 | 302 | |||
| Single | Dartmouth | 400 | 37 | 95 | 900 | 900 | 493 | 410 | 272 | 259 | 300 | 329 | |||
| Single | 브라운 | 450 | 37 | 95 | 940 | 940 | 547 | 439 | 295 | - | - | - | |||
| Single | Emory | 500 | 37 | 95 | 980 | 980 | 601 | 464 | 318 | 299 | 344 | 378 | |||
| Single | Duke | 600 | 61 | 110 | 1090 | 1090 | 725 | 514 | 355 | 328 | 377 | 416 | |||
| Single | Furman | 700 | 61 | 110 | 1160 | 1160 | 830 | 549 | 386 | 362 | 416 | 459 | |||
| Single | Sewanee | 750 | 61 | 110 | 1190 | 1190 | 883 | 567 | 403 | 368 | 427 | 470 | |||
| Single | Fordham | 1000 | 61 | 110 | 1340 | 1340 | 1144 | 665 | 492 | 431 | 494 | 540 | |||
| Duplex | Bard | 8 | 7 | 60 | 8 | 7 | 60 | 262 | 524 | 76 | 70 | 55 | |||
| Duplex | Claflin | 6 | 7 | 60 | 6 | 7 | 60 | 298 | 596 | 91 | 95 | 70 | |||
| Duplex | Delgado | 4 | 7 | 60 | 4 | 7 | 60 | 345 | 690 | 129 | 125 | 90 | |||
| Duplex | Everett | 2 | 7 | 60 | 2 | 7 | 60 | 403 | 806 | 189 | 187 | 100 | |||
| Triplex | Erskine | 6 | 7 | 60 | 6 | 7 | 60 | 298 | 644 | 136 | 95 | 70 | |||
| Triplex | Vassar | 4 | 7 | 60 | 4 | 7 | 60 | 345 | 745 | 194 | 125 | 90 | |||
| Triplex | Stephens | 2 | 7 | 60 | 4 | 7 | 60 | 403 | 870 | 260 | 165 | 120 | |||
| Triplex | Ramapo | 2 | 7 | 60 | 2 | 7 | 60 | 403 | 870 | 290 | 165 | 120 | |||
| Triplex | Brenau | 1/0 | 19 | 80 | 2 | 7 | 60 | 512 | 1106 | 409 | 215 | 160 | |||
| Triplex | Bergen | 1/0 | 19 | 80 | 1/0 | 19 | 80 | 512 | 1106 | 476 | 215 | 160 | |||
| Triplex | Converse | 2/0 | 19 | 80 | 1 | 19 | 80 | 555 | 1199 | 490 | 245 | 180 | |||
| Triplex | Hunter | 2/0 | 19 | 80 | 2/0 | 19 | 80 | 555 | 1199 | 540 | 245 | 180 | |||
| Triplex | Hollins | 3/0 | 19 | 80 | 1/0 | 19 | 80 | 603 | 1302 | 586 | 280 | 205 | |||
| Triplex | Sweetbriar | 4/0 | 19 | 80 | 2/0 | 19 | 80 | 658 | 1421 | 740 | 315 | 240 | |||
| Triplex | Monmouth | 4/0 | 19 | 80 | 4/0 | 19 | 80 | 658 | 1421 | 847 | 315 | 240 | |||
| Triplex | Pratt | 250 | 37 | 95 | 3/0 | 19 | 80 | 732 | 1581 | 857 | 345 | 265 | |||
| Triplex | Wesleyan | 350 | 37 | 95 | 4/0 | 19 | 80 | 831 | 1795 | 1135 | 415 | 320 | |||
| Triplex | Rider | 500 | 37 | 95 | 350 | 37 | 95 | 980 | 2117 | 1248 | 495 | 395 | |||
| Triplex | Fairfield | 750 | 61 | 110 | 500 | 37 | 95 | 1188 | 2860 | 2304 | 615 | 525 | |||
| Quadruplex | Tulsa | 4 | 7 | 60 | 4 | 7 | 60 | 345 | 833 | 258 | 120 | 85 | |||
| Quadruplex | Dyke | 2 | 7 | 60 | 4 | 7 | 60 | 403 | 973 | 367 | 155 | 115 | |||
| Quadruplex | Wittenberg | 2 | 7 | 60 | 2 | 7 | 60 | 403 | 973 | 375 | 155 | 115 | |||
| Quadruplex | Notre Dame | 1/0 | 19 | 80 | 2 | 7 | 60 | 512 | 1236 | 574 | 200 | 150 | |||
| Quadruplex | Purdue | 1/0 | 19 | 80 | 1/0 | 19 | 80 | 512 | 1236 | 596 | 200 | 150 | |||
| Quadruplex | Syracuse | 2/0 | 19 | 80 | 1 | 19 | 80 | 555 | 1340 | 664 | 225 | 170 | |||
| Quadruplex | Lafayette | 2/0 | 19 | 80 | 2/0 | 19 | 80 | 555 | 1340 | 720 | 225 | 170 | |||
| Quadruplex | Swarthmore | 3/0 | 19 | 80 | 1/0 | 19 | 80 | 603 | 1456 | 805 | 250 | 195 | |||
| Quadruplex | Davidson | 3/0 | 19 | 80 | 3/0 | 19 | 80 | 603 | 1456 | 874 | 250 | 195 | |||
| Quadruplex | Wake Forest | 4/0 | 19 | 80 | 2/0 | 19 | 80 | 658 | 1588 | 1036 | 290 | 225 | |||
| Quadruplex | Earlham | 4/0 | 19 | 80 | 4/0 | 19 | 80 | 658 | 1588 | 1066 | 290 | 225 | |||
| Quadruplex | Rust | 250 | 37 | 95 | 3/0 | 19 | 80 | 760 | 1830 | 1213 | 325 | 210 | |||
| Quadruplex | Slippery Rock | 350 | 37 | 95 | 4/0 | 19 | 80 | 831 | 1945 | 1544 | 385 | 305 | |||
| Quadruplex | Wofford | 500 | 37 | 95 | 350 | 37 | 95 | 990 | 2390 | 2251 | 467 | 420 | |||
| Quadruplex | Windham | 750 | 61 | 110 | 500 | 37 | 95 | 1200 | 2890 | 3266 | 615 | 492 |
| 카테고리 | 코드 이름 | Phase AWG | Phase Stranding | Phase Insulation Thickness | Neutral AWG | Neutral Stranding | Neutral Insulation Thickness | Diameter Single Phase (mils) | Diameter Complete Cable (mils) | Weight (lbs/kft) | Ampacity Direct Burial | Ampacity In Ducts |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| DUPLEX | Bard | 8 | 7 | 60 | 8 | 7 | 60 | 262 | 524 | 76 | 70 | 55 |
| DUPLEX | Clafin | 6 | 7 | 60 | 6 | 7 | 60 | 298 | 596 | 91 | 95 | 70 |
| DUPLEX | Delgado | 4 | 7 | 60 | 4 | 7 | 60 | 345 | 690 | 129 | 125 | 90 |
| DUPLEX | Everett | 2 | 7 | 60 | 2 | 7 | 60 | 403 | 806 | 189 | 187 | 100 |
| TRIPLEX | Erskine | 6 | 7 | 60 | 6 | 7 | 60 | 298 | 644 | 136 | 95 | 70 |
| TRIPLEX | Vassar | 4 | 7 | 60 | 4 | 7 | 60 | 345 | 745 | 194 | 125 | 90 |
| TRIPLEX | Stephens | 2 | 7 | 60 | 4 | 7 | 60 | 403 | 870 | 260 | 165 | 120 |
| TRIPLEX | Ramapo | 2 | 7 | 60 | 2 | 7 | 60 | 403 | 870 | 290 | 165 | 120 |
| TRIPLEX | Brenau | 1/0 | 19 | 80 | 2 | 7 | 60 | 512 | 1106 | 409 | 215 | 160 |
| TRIPLEX | Bergen | 1/0 | 19 | 80 | 1/0 | 19 | 80 | 512 | 1106 | 476 | 215 | 160 |
| TRIPLEX | Converse | 2/0 | 19 | 80 | 1 | 19 | 80 | 555 | 1199 | 490 | 245 | 180 |
| TRIPLEX | Hunter | 2/0 | 19 | 80 | 2/0 | 19 | 80 | 555 | 1199 | 540 | 245 | 180 |
| TRIPLEX | Hollins | 3/0 | 19 | 80 | 1/0 | 19 | 80 | 603 | 1302 | 586 | 280 | 205 |
| TRIPLEX | Sweetbriar | 4/0 | 19 | 80 | 2/0 | 19 | 80 | 658 | 1421 | 740 | 315 | 240 |
| TRIPLEX | Monmouth | 4/0 | 19 | 80 | 4/0 | 19 | 80 | 658 | 1421 | 847 | 315 | 240 |
| TRIPLEX | Pratt | 250 | 37 | 95 | 3/0 | 19 | 80 | 732 | 1581 | 857 | 345 | 265 |
| TRIPLEX | Wesleyan | 350 | 37 | 95 | 4/0 | 19 | 80 | 831 | 1795 | 1135 | 415 | 320 |
| TRIPLEX | Rider | 500 | 37 | 95 | 350 | 37 | 95 | 980 | 2117 | 1248 | 495 | 395 |
| TRIPLEX | Fairfield | 750 | 61 | 110 | 500 | 37 | 95 | 1188 | 2860 | 2304 | 615 | 525 |
| QUADRUPLEX | Tulsa | 4 | 7 | 60 | 4 | 7 | 60 | 345 | 833 | 258 | 120 | 85 |
| QUADRUPLEX | Dyke | 2 | 7 | 60 | 4 | 7 | 60 | 403 | 973 | 367 | 155 | 115 |
| QUADRUPLEX | Wittenberg | 2 | 7 | 60 | 2 | 7 | 60 | 403 | 973 | 375 | 155 | 115 |
| QUADRUPLEX | Notre Dame | 1/0 | 19 | 80 | 2 | 7 | 60 | 512 | 1236 | 574 | 200 | 150 |
| QUADRUPLEX | Purdue | 1/0 | 19 | 80 | 1/0 | 19 | 80 | 512 | 1236 | 596 | 200 | 150 |
| QUADRUPLEX | Syracuse | 2/0 | 19 | 80 | 1 | 19 | 80 | 555 | 1340 | 664 | 225 | 170 |
| QUADRUPLEX | Lafayette | 2/0 | 19 | 80 | 2/0 | 19 | 80 | 555 | 1340 | 720 | 225 | 170 |
| QUADRUPLEX | Swarthmore | 3/0 | 19 | 80 | 1/0 | 19 | 80 | 603 | 1456 | 805 | 250 | 195 |
| QUADRUPLEX | Davidson | 3/0 | 19 | 80 | 3/0 | 19 | 80 | 603 | 1456 | 874 | 250 | 195 |
| QUADRUPLEX | Wake Forest | 4/0 | 19 | 80 | 2/0 | 19 | 80 | 658 | 1588 | 1036 | 290 | 225 |
| QUADRUPLEX | Earlham | 4/0 | 19 | 80 | 4/0 | 19 | 80 | 658 | 1588 | 1066 | 290 | 225 |
| QUADRUPLEX | Rust | 250 | 37 | 95 | 3/0 | 19 | 80 | 760 | 1830 | 1213 | 325 | 210 |
| QUADRUPLEX | Slippery Rock | 350 | 37 | 95 | 4/0 | 19 | 80 | 831 | 1945 | 1544 | 385 | 305 |
| QUADRUPLEX | Wofford | 500 | 37 | 95 | 350 | 37 | 95 | 990 | 2390 | 2251 | 467 | 420 |
| QUADRUPLEX | Windham | 750 | 61 | 110 | 500 | 37 | 95 | 1200 | 2890 | 3266 | 615 | 492 |
| 코드 이름 | Phase Size (AWG/kcmil) | Phase Stranding | Phase Insulation Thickness (mils) | Neutral Size (AWG/kcmil) | Neutral Stranding | Neutral Insulation Thickness (mils) | Single Phase Cond. Diameter (mils) | Complete Cable Diameter (mils) | Weight (lb/kft) | Ampacity Direct Burial | Ampacity In Ducts |
|---|---|---|---|---|---|---|---|---|---|---|---|
| VASSAR-8000 | 4 | 7 | 60 | 4 | 7 | 60 | 345 | 745 | 191 | 125 | 90 |
| STEPHENS-8000 | 2 | 7 | 60 | 4 | 7 | 60 | 403 | 870 | 246 | 165 | 120 |
| RAMAPO-8000 | 2 | 7 | 60 | 2 | 7 | 60 | 403 | 870 | 290 | 165 | 120 |
| BRENAU-8000 | 1/0 | 19 | 80 | 2 | 7 | 60 | 512 | 1106 | 389 | 215 | 160 |
| BERGEN-8000 | 1/0 | 19 | 80 | 1/0 | 19 | 80 | 512 | 1106 | 476 | 215 | 160 |
| CONVERSE-8000 | 2/0 | 19 | 80 | 1 | 19 | 80 | 555 | 1199 | 483 | 245 | 180 |
| HUNTER-8000 | 2/0 | 11 | 80 | 2/0 | 11 | 80 | 555 | 1199 | 545 | 245 | 180 |
| SWEETBRIAR-8000 | 4/0 | 19 | 80 | 2/0 | 19 | 80 | 658 | 1421 | 715 | 315 | 240 |
| MONMOUTH-8000 | 4/0 | 19 | 80 | 4/0 | 19 | 80 | 658 | 1421 | 802 | 315 | 240 |
| PRATT-8000 | 250 | 37 | 95 | 3/0 | 19 | 80 | 732 | 1581 | 867 | 345 | 265 |
| WESLEYAN-8000 | 350 | 37 | 95 | 4/0 | 19 | 80 | 831 | 1795 | 1165 | 415 | 320 |
-
Production Processes Of Aerial Bundled Cable
공중 케이블 제조 인프라는 폐쇄 루프 디지털 자동화 시스템을 운영하여 도체 연선,절연 압출 및 최종 피복을 연속 워크플로우로 통합합니다. 공정 안정성은 임베디드 센서 어레이에 의존하여 압출 파라미터를 실시간으로 추적하여 수동 변동을 제거합니다. 이중 축 레이저 직경 게이지 및 고전압 스파크 테스터를 포함한 특정 인라인 하드웨어를 통해 품질 검증을 시행하는 반면,물리적 실험실에서는 파괴 인장 및 신장 분석을 실시하여 선적 전에 국제 표준 준수 여부를 확인합니다.
배송용 포장
다양한 운송 요구를 충족시키기 위해 사용할 수있는 포장 방법이 많이 있습니다.
질문이 더 있으십니까?
Q: 직접 매장 능력?
답: 검증된. Engineered specifically for Direct Earth Burial 그리고 Ducting (Wet or Dry soil conditions).
Q: Thermal Rating?
답: 90°C (Continuous Normal Operation).
Q: Neutral Conductor Identification?
답: Visual Coding: Marked with Yellow Striping (or Full Yellow Jacket) to prevent phasing errors.
Q: Alloy Specifications?
답: 재료: 1350-H19 Aluminum 또는 AA-8000 Series Alloy (Dependent on specific configuration).
Q: Chemical/Moisture Resistance?
답: High Resilience. X-1000 X 1000 X 1000 X 1000 X 1000 X 1000 X 1000 X 1000 X XLPE dielectric system blocks heat, ozone, oil, and common sub-surface chemical agents.
Q: UL Certification?
답: 규정 준수: Single conductors are UL Listed (Type USE-2) for underground service entrance.
Q: Above-Ground Application?
답: Restricted. Primary design is for underground networks. Above-ground installation (risers) requires verification of local code/sunlight resistance ratings.
Q: How to Request Pricing/Specs?
답: Action: Click the “문의하기” button or view the Seller Profile directly for official quotations.