N2XB(AL)Y/NA2XB(AL)Y
0.6/1kV Single Core XLPE Insulation Aluminum Tape Armoured and PVC Jacket power cable
- 指揮 : Stranded Copper or Aluminium
- 絕緣 :XLPE
- Bedding : PVC or non-hygroscopic filler (depending on size)
- 鎧甲 : Aluminum Tape Armoured
- 外護套 : PVC (Type ST2, IEC 60502-1)
- 使用客製化解決方案進行快速樣品處理
- 高品質材料
- 經濟實惠的價格選擇
- 全球交付
- 為了更好地保護數據,請確保所有上傳都是安全的
平均至少節省 30%
-
產品說明
N2XB(AL)Y/NA2XB(AL)Y: Product Description and Specifications
的 N2XB(AL)Y 系列是為之而建的 單核 runs. The critical detail here is the Armor. 我們使用 Aluminum Tape (ATA), not Steel. Why? If you wrap a single-core AC cable in magnetic steel, it acts like an induction coil and 過熱. Aluminum is non-magnetic. It gives you the crush protection you need without cooking the cable. Paired with XLPE insulation (90°C rated), it’s the safe, efficient way to run high currents underground.
-
優點
N2XB(AL)Y/NA2XB(AL)Y : Benefits and Features
90°C Headroom: 我們使用 XLPE, not PVC. That means you get a higher current rating and the cable won’t degrade when things get hot.
Why Aluminum Tape (ATA)? Simple physics. You can’t use steel on a single-core cable—it creates a magnetic field that overheats the armor. 鋁是 非磁性, so it stops the heating issue dead.
Install Anywhere: Ducts, power stations, or buried right in the dirt. It’s built for all of it.
16mm² to 800mm²: From standard runs to massive main feeders, we cover the whole spread.
IEC 60502-1: We don’t guess. The outer sheath and build strictly follow the global standard.
尺寸/參數
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max (Ω/km) | AC Resistance at 90°C Max (Ω/km) | 電感三葉形形成(mH/km) | 電感平坦形成(mH/km) | Trefoil Formation - in air Max (A) | Trefoil Formation - in ground Max (A) | Flat Formation - in air Max (A) | Flat Formation - in ground Max (A) | Short circuit current at 1 sec Max (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.15 | 1.466 | 0.412 | 0.458 | 118 | 118 | 121 | 121 | 2.29 |
| 25 | 0.727 | 0.927 | 0.366 | 0.412 | 154 | 153 | 158 | 157 | 3.58 |
| 35 | 0.524 | 0.668 | 0.349 | 0.395 | 188 | 183 | 193 | 188 | 5.01 |
| 50 | 0.387 | 0.494 | 0.332 | 0.378 | 229 | 217 | 235 | 223 | 7.15 |
| 70 | 0.268 | 0.342 | 0.318 | 0.364 | 287 | 265 | 295 | 272 | 10.01 |
| 95 | 0.193 | 0.247 | 0.304 | 0.350 | 352 | 317 | 361 | 324 | 13.59 |
| 120 | 0.153 | 0.196 | 0.296 | 0.342 | 407 | 359 | 418 | 367 | 17.16 |
| 150 | 0.124 | 0.159 | 0.292 | 0.338 | 465 | 402 | 476 | 410 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.286 | 0.332 | 537 | 453 | 549 | 461 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.277 | 0.323 | 636 | 523 | 648 | 529 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.272 | 0.318 | 728 | 585 | 739 | 590 | 42.90 |
| 400 | 0.0470 | 0.064 | 0.270 | 0.317 | 838 | 655 | 846 | 657 | 57.20 |
| 500 | 0.0366 | 0.052 | 0.266 | 0.312 | 960 | 731 | 964 | 728 | 71.50 |
| 630 | 0.0283 | 0.042 | 0.261 | 0.307 | 1092 | 807 | 1087 | 797 | 90.09 |
| 800 | 0.0221 | 0.035 | 0.259 | 0.305 | 1216 | 877 | 1202 | 858 | 114.40 |
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max (Ω/km) | AC Resistance at 90°C Max (Ω/km) | 電感三葉形形成(mH/km) | 電感平坦形成(mH/km) | Trefoil Formation - in air Max (A) | Trefoil Formation - in ground Max (A) | Flat Formation - in air Max (A) | Flat Formation - in ground Max (A) | Short circuit current at 1 sec Max (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.91 | 2.449 | 0.404 | 0.450 | 92 | 92 | 94 | 101 | 1.50 |
| 25 | 1.20 | 1.539 | 0.367 | 0.413 | 120 | 119 | 123 | 122 | 2.35 |
| 35 | 0.868 | 1.113 | 0.348 | 0.394 | 146 | 142 | 150 | 146 | 3.29 |
| 50 | 0.641 | 0.822 | 0.332 | 0.378 | 177 | 168 | 182 | 173 | 4.70 |
| 70 | 0.443 | 0.568 | 0.316 | 0.363 | 224 | 206 | 230 | 212 | 6.58 |
| 95 | 0.320 | 0.411 | 0.304 | 0.350 | 274 | 246 | 281 | 253 | 8.93 |
| 120 | 0.253 | 0.325 | 0.298 | 0.344 | 316 | 280 | 325 | 286 | 11.28 |
| 150 | 0.206 | 0.265 | 0.290 | 0.336 | 364 | 314 | 374 | 321 | 14.10 |
| 185 | 0.164 | 0.211 | 0.285 | 0.332 | 421 | 355 | 432 | 363 | 17.39 |
| 240 | 0.125 | 0.162 | 0.276 | 0.323 | 502 | 412 | 514 | 419 | 22.56 |
| 300 | 0.100 | 0.130 | 0.272 | 0.318 | 577 | 463 | 589 | 470 | 28.20 |
| 400 | 0.0778 | 0.102 | 0.266 | 0.312 | 685 | 530 | 697 | 535 | 37.60 |
| 500 | 0.0605 | 0.081 | 0.264 | 0.310 | 786 | 597 | 796 | 600 | 47.00 |
| 630 | 0.0469 | 0.064 | 0.261 | 0.307 | 906 | 670 | 913 | 670 | 59.22 |
| 800 | 0.0367 | 0.052 | 0.259 | 0.305 | 1028 | 743 | 1028 | 737 | 75.20 |
-
電纜的生產流程
確保卓越的品質, ,喬卡 經營 完全數位化和自動化的生產線 電源電纜. 具體來說, ,這個綜合的工作流程 覆蓋 導體絞合、絕緣擠壓、金屬屏蔽和最終護套。. 而且, ,智能係統 主動監控 每個階段都確保穩定的性能和一致的產品品質。. 另外, ,工廠 利用 先進的測試設施,如局部放電測試、拉伸測試和火花測試。. 因此, ,這些嚴格的措施 保證 每條交付的電纜都嚴格符合國際標準。.
裝運包裝
為了滿足各種運輸需求,可以使用多種包裝方法。.
還有更多問題嗎?
Q: N2XB(AL)Y vs. NA2XB(AL)Y: What’s the difference?
答: 只是導體金屬。. N2XB(AL)Y 是銅。. NA2XB(AL)Y is Aluminum. Structurally? They are twins. Aluminum is just lighter and saves you budget.
Q: Why use Aluminum Armor (ATA) instead of Steel?
答: Physics. Since this is a Single Core cable, magnetic steel armor would turn into an induction coil and overheat the cable. Aluminum is non-magnetic. It gives you protection without the heat.
Q:額定電壓?
答: 標準低壓: 0.6/1kV.
Q: Max operating temp?
答: 90°C. Thanks to the XLPE insulation, it handles heat way better than PVC cables.
Q: Do you stock big sizes?
答: Huge ones. We go from standard 16mm² all the way up to massive 800mm² feeders.
Q: Is the sheath durable?
答: 是的。. It’s Type ST2 PVC. Built to IEC 60502-1 standards, so it handles abrasion and trench conditions fine.
Q: How strong is it against short circuits?
答: It’s a beast. Take the 800mm² Copper version—it can survive a massive 114.40 kA spike for a full second.
Q:我可以把它埋在地下嗎?
答: 絕對地。. The Aluminum Tape Armor isn’t just for looks—it’s there to protect the cable in the ground. Direct burial is fully supported.