N2XSB(AL)Y/NA2XSB(AL)Y
3.6KV-35KV XLPE Insulation Aluminum Tape Armoured and PVC Jacket power cable
- Dirigent: Copper or Aluminum(Class 2 according to IEC 60502-2).
- Isolatie : XLPE
- Metallic Screen : Copper Tape
- Separation Layer : Non-hygroscopic Tape.
- Innerlijke schede : PVC
- Armour : Aluminum Tape Armor (ATA).
- Buitenschede : PVC
- Kleur : Usually Red or Black.
- Snelle monsterverwerking met oplossingen op maat
- Hoogwaardige materialen
- Betaalbare Prijs Opties
- Global Delivery
- Zorg er voor een betere gegevensbescherming voor dat alle uploads veilig zijn
Bespaar gemiddeld minimaal 30%
-
Productbeschrijving
N2XSB(AL)Y/NA2XSB(AL)Y : Product Description and Specifications
The N2XSB(AL)Y series is a dedicated Medium Voltage (3.6kV–35kV) cable for power transmission. It combines a high-conductivity Copper conductor with XLPE insulation. Crucially, the mechanical protection uses Aluminum Tape Armor (ATA) rather than steel. Since Aluminum is non-magnetic, this design eliminates the risk of eddy current overheating in single-core circuits while still providing the crush resistance required for direct underground burial. The assembly is finished with a weather-resistant PVC sheath, suitable for industrial grids and renewable energy infrastructure.
-
Voordelen
N2XSB(AL)Y/NA2XSB(AL)Y : Benefits and Features
90°C Rated: XLPE handles the heat. It runs hotter and harder than standard PVC cables.
Aluminum Tape Armor: A physical shield. It stops crushing rocks and keeps hungry rodents from chewing through.
Weatherproof: Sun, rain, or mud? No problem. The jacket shrugs it off.
25-Year Life: TUV certified. Install it and forget about it for a quarter-century.
Install Anywhere: Direct burial, trenches, or even floating solar rigs. It handles it all.
Afmetingen/parameters
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max (Ω/km) | AC Resistance at 90°C Max (Ω/km) | Inductance Trefoil formation (mH/km) | Inductance Flat formation (mH/km) | Current Capacity Trefoil - in air (A) | Current Capacity Trefoil - in ground (A) | Current Capacity Flat - in air (A) | Current Capacity Flat - in ground (A) | Short circuit current at 1 sec - Conductor Max (kA) | Short circuit current at 1 sec - Screen Max (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.454 | 0.500 | 166 | 153 | 170 | 156 | 3.58 | 1.14 |
| 35 | 0.524 | 0.668 | 0.431 | 0.477 | 201 | 183 | 206 | 187 | 5.01 | 1.14 |
| 50 | 0.387 | 0.494 | 0.413 | 0.459 | 240 | 216 | 246 | 221 | 7.15 | 1.14 |
| 70 | 0.268 | 0.342 | 0.389 | 0.435 | 299 | 264 | 307 | 270 | 10.01 | 1.14 |
| 95 | 0.193 | 0.247 | 0.373 | 0.419 | 363 | 315 | 372 | 322 | 13.59 | 1.14 |
| 120 | 0.153 | 0.196 | 0.358 | 0.404 | 418 | 358 | 428 | 365 | 17.16 | 1.14 |
| 150 | 0.124 | 0.159 | 0.347 | 0.393 | 476 | 401 | 487 | 410 | 21.45 | 1.14 |
| 185 | 0.0991 | 0.128 | 0.338 | 0.385 | 545 | 452 | 557 | 461 | 26.46 | 1.14 |
| 240 | 0.0754 | 0.098 | 0.326 | 0.372 | 642 | 523 | 657 | 532 | 34.32 | 1.14 |
| 300 | 0.0601 | 0.079 | 0.316 | 0.362 | 734 | 588 | 750 | 598 | 42.90 | 1.14 |
| 400 | 0.0470 | 0.063 | 0.305 | 0.351 | 852 | 666 | 869 | 677 | 57.20 | 1.14 |
| 500 | 0.0366 | 0.051 | 0.297 | 0.343 | 980 | 750 | 997 | 760 | 71.50 | 1.14 |
| 630 | 0.0283 | 0.041 | 0.289 | 0.335 | 1120 | 840 | 1137 | 848 | 90.09 | 1.14 |
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max (Ω/km) | AC Resistance at 90°C Max (Ω/km) | Inductance Trefoil formation (mH/km) | Inductance Flat formation (mH/km) | Current Capacity Trefoil - in air (A) | Current Capacity Trefoil - in ground (A) | Current Capacity Flat - in air (A) | Current Capacity Flat - in ground (A) | Short circuit current at 1 sec - Conductor Max (kA) | Short circuit current at 1 sec - Screen Max (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.437 | 0.484 | 164 | 153 | 168 | 157 | 3.58 | 1.14 |
| 35 | 0.524 | 0.668 | 0.415 | 0.461 | 199 | 183 | 204 | 188 | 5.01 | 1.14 |
| 50 | 0.387 | 0.494 | 0.398 | 0.444 | 237 | 216 | 243 | 221 | 7.15 | 1.14 |
| 70 | 0.268 | 0.342 | 0.374 | 0.421 | 296 | 264 | 304 | 270 | 10.01 | 1.14 |
| 95 | 0.193 | 0.247 | 0.358 | 0.404 | 360 | 316 | 369 | 323 | 13.59 | 1.14 |
| 120 | 0.153 | 0.196 | 0.346 | 0.392 | 416 | 358 | 426 | 366 | 17.16 | 1.14 |
| 150 | 0.124 | 0.159 | 0.334 | 0.380 | 473 | 402 | 484 | 410 | 21.45 | 1.14 |
| 185 | 0.0991 | 0.128 | 0.325 | 0.371 | 541 | 453 | 554 | 462 | 26.46 | 1.14 |
| 240 | 0.0754 | 0.098 | 0.316 | 0.362 | 639 | 523 | 654 | 533 | 34.32 | 1.14 |
| 300 | 0.0601 | 0.079 | 0.309 | 0.356 | 733 | 588 | 748 | 598 | 42.90 | 1.14 |
| 400 | 0.0470 | 0.063 | 0.300 | 0.346 | 851 | 667 | 868 | 677 | 57.20 | 1.14 |
| 500 | 0.0366 | 0.051 | 0.294 | 0.341 | 979 | 751 | 997 | 760 | 71.50 | 1.14 |
| 630 | 0.0283 | 0.041 | 0.286 | 0.332 | 1120 | 840 | 1136 | 848 | 90.09 | 1.14 |
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max (Ω/km) | AC Resistance at 90°C Max (Ω/km) | Inductance Trefoil formation (mH/km) | Inductance Flat formation (mH/km) | Current Capacity Trefoil - in air (A) | Current Capacity Trefoil - in ground (A) | Current Capacity Flat - in air (A) | Current Capacity Flat - in ground (A) | Short circuit current at 1 sec - Conductor Max (kA) | Short circuit current at 1 sec - Screen Max (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.473 | 0.519 | 168 | 153 | 172 | 156 | 3.58 | 1.14 |
| 35 | 0.524 | 0.668 | 0.448 | 0.495 | 203 | 183 | 208 | 187 | 5.01 | 1.14 |
| 50 | 0.387 | 0.494 | 0.430 | 0.476 | 242 | 216 | 248 | 220 | 7.15 | 1.14 |
| 70 | 0.268 | 0.342 | 0.405 | 0.451 | 302 | 263 | 309 | 269 | 10.01 | 1.14 |
| 95 | 0.193 | 0.247 | 0.387 | 0.433 | 366 | 315 | 374 | 321 | 13.59 | 1.14 |
| 120 | 0.153 | 0.196 | 0.376 | 0.422 | 422 | 357 | 431 | 364 | 17.16 | 1.14 |
| 150 | 0.124 | 0.159 | 0.363 | 0.409 | 479 | 401 | 490 | 409 | 21.45 | 1.14 |
| 185 | 0.0991 | 0.128 | 0.352 | 0.399 | 548 | 452 | 560 | 460 | 26.46 | 1.14 |
| 240 | 0.0754 | 0.098 | 0.338 | 0.385 | 645 | 522 | 659 | 532 | 34.32 | 1.14 |
| 300 | 0.0601 | 0.079 | 0.327 | 0.374 | 738 | 588 | 753 | 598 | 42.90 | 1.14 |
| 400 | 0.0470 | 0.063 | 0.317 | 0.363 | 855 | 667 | 871 | 676 | 57.20 | 1.14 |
| 500 | 0.0366 | 0.050 | 0.307 | 0.353 | 984 | 752 | 1000 | 761 | 71.50 | 1.14 |
| 630 | 0.0283 | 0.041 | 0.297 | 0.344 | 1125 | 842 | 1141 | 850 | 90.09 | 1.14 |
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max (Ω/km) | AC Resistance at 90°C Max (Ω/km) | Inductance Trefoil formation (mH/km) | Inductance Flat formation (mH/km) | Current Capacity Trefoil - in air (A) | Current Capacity Trefoil - in ground (A) | Current Capacity Flat - in air (A) | Current Capacity Flat - in ground (A) | Short circuit current at 1 sec - Conductor Max (kA) | Short circuit current at 1 sec - Screen Max (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 35 | 0.524 | 0.668 | 0.465 | 0.511 | 205 | 183 | 210 | 187 | 5.01 | 1.14 |
| 50 | 0.387 | 0.494 | 0.445 | 0.491 | 244 | 215 | 249 | 220 | 7.15 | 1.14 |
| 70 | 0.268 | 0.342 | 0.420 | 0.466 | 304 | 263 | 311 | 269 | 10.01 | 1.14 |
| 95 | 0.193 | 0.247 | 0.404 | 0.450 | 368 | 314 | 376 | 320 | 13.59 | 1.14 |
| 120 | 0.153 | 0.196 | 0.389 | 0.435 | 424 | 357 | 433 | 364 | 17.16 | 1.14 |
| 150 | 0.124 | 0.159 | 0.376 | 0.422 | 482 | 400 | 492 | 408 | 21.45 | 1.14 |
| 185 | 0.0991 | 0.127 | 0.364 | 0.410 | 550 | 451 | 562 | 460 | 26.46 | 1.14 |
| 240 | 0.0754 | 0.098 | 0.349 | 0.395 | 648 | 522 | 661 | 532 | 34.32 | 1.14 |
| 300 | 0.0601 | 0.079 | 0.338 | 0.384 | 740 | 588 | 755 | 597 | 42.90 | 1.14 |
| 400 | 0.0470 | 0.063 | 0.327 | 0.373 | 858 | 667 | 873 | 676 | 57.20 | 1.14 |
| 500 | 0.0366 | 0.050 | 0.316 | 0.362 | 986 | 752 | 1002 | 761 | 71.50 | 1.14 |
| 630 | 0.0283 | 0.041 | 0.306 | 0.352 | 1128 | 843 | 1143 | 850 | 90.09 | 1.14 |
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max (Ω/km) | AC Resistance at 90°C Max (Ω/km) | Inductance Trefoil formation (mH/km) | Inductance Flat formation (mH/km) | Current Capacity Trefoil - in air (A) | Current Capacity Trefoil - in ground (A) | Current Capacity Flat - in air (A) | Current Capacity Flat - in ground (A) | Short circuit current at 1 sec - Conductor Max (kA) | Short circuit current at 1 sec - Screen Max (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 50 | 0.387 | 0.494 | 0.481 | 0.528 | 248 | 214 | 253 | 219 | 7.15 | 1.14 |
| 70 | 0.268 | 0.342 | 0.453 | 0.500 | 308 | 262 | 314 | 268 | 10.01 | 1.14 |
| 95 | 0.193 | 0.247 | 0.434 | 0.480 | 372 | 313 | 380 | 319 | 13.59 | 1.14 |
| 120 | 0.153 | 0.196 | 0.417 | 0.463 | 428 | 356 | 437 | 363 | 17.16 | 1.14 |
| 150 | 0.124 | 0.159 | 0.403 | 0.449 | 486 | 399 | 496 | 407 | 21.45 | 1.14 |
| 185 | 0.0991 | 0.127 | 0.391 | 0.438 | 554 | 450 | 565 | 459 | 26.46 | 1.14 |
| 240 | 0.0754 | 0.098 | 0.376 | 0.422 | 652 | 521 | 664 | 530 | 34.32 | 1.14 |
| 300 | 0.0601 | 0.078 | 0.364 | 0.410 | 744 | 587 | 757 | 596 | 42.90 | 1.14 |
| 400 | 0.0470 | 0.062 | 0.349 | 0.395 | 861 | 666 | 876 | 676 | 57.20 | 1.14 |
| 500 | 0.0366 | 0.050 | 0.337 | 0.383 | 990 | 753 | 1005 | 761 | 71.50 | 1.14 |
| 630 | 0.0283 | 0.040 | 0.327 | 0.373 | 1132 | 845 | 1145 | 852 | 90.09 | 1.14 |
-
Productieprocessen van stroomkabel
Om superieure kwaliteit te verzekeren, JOCA opereert volledig gedigitaliseerde en geautomatiseerde productielijnen voor stroomkabels. Specifiek, deze uitgebreide workflow covers geleiderstreng, isolatie-extrusie, metaalafscherming en eindafdekking. Bovendien, intelligente systemen actief monitoren elke fase om stabiele prestaties en consistente productkwaliteit te garanderen. Daarnaast, de fabriek gebruikt geavanceerde testfaciliteiten, zoals gedeeltelijke ontladingstests, trekproeven en vonktesten. Bijgevolg, deze rigoureuze maatregelen garantie dat elke geleverde kabel strikt voldoet aan internationale normen.
Verpakking voor verzending
Om aan verschillende transportbehoeften te voldoen, zijn er veel verpakkingsmethoden die kunnen worden gebruikt.
Heb je nog meer vragen?
Q: Voltage range?
A: It handles the full Medium Voltage spread: 3.6kV all the way to 35kV.
Q: Isolatiemateriaal?
A: XLPE. It beats PVC hands down because it can run hotter (90°C) without degrading.
Q: Why use Aluminum Tape Armor?
A: Protection without the weight. It stops rats from chewing the core and protects against light impact. Plus, since it’s aluminum, it won’t overheat magnetically like steel does on single-core cables.
Q: Can I bury it?
A: Go for it. That’s what the armor is for. Dig the trench, drop it in, and cover it up.
Q: Max temp?
A: It runs happily at 90°C continuous. No sweat.
Q: Where can I install it?
A: Pretty much anywhere. Solar farms, rooftops, or even floating PV rigs. It’s built for the outdoors.
Q: Conductor type?
A: High-grade Stranded Copper. We don’t skimp on the metal.
Q: How long will it last?
A: It’s certified for 25 jaar. Install it properly, and you won’t have to touch it for decades.