Blocco frodi

JOCA

N2XRY/NA2XRY

cavo di alimentazione con rivestimento in acciaio con isolamento XLPE multi nucleo da 0,6/1kV

Conduttore: copper conductor or aluminium conductor 

Insulation : Extruded layer of Cross-linked Polyethylene (XLPE) to IEC 60502-1.

Bedding : Extruded layer of Polyvinyl Chloride (PVC) – Type (ST2) to IEC 60502-1.

Armouring : Single layer of round galvanized steel wires.

Outer Jacket : Extruded layer of Polyvinyl Chloride (PVC) – Type (ST2) to IEC 60502-1.

 Risparmia almeno 30% in media

N2XRY-NA2XRY_1
  • icona

    Descrizione del prodotto

    N2XRY/NA2XRY : Product Description and Specifications

Il N2XRY (Copper) e NA2XRY (Aluminum) series are your heavy-duty workhorses for multi-core distribution (0,6/1kV). The key feature here is the SWA (Steel Wire Armor). Unlike unarmored cables, the galvanized steel wires provide a serious mechanical shield, meaning you can bury these directly or run them in high-risk industrial zones without worrying about crushing or impact. We use Isolamento XLPE to give you that higher 90 °C thermal rating. Pro tip: For larger sizes (like 50mm² and up), ask for Sector-Shaped conductors. They reduce the overall cable diameter and weight, making it much easier to gland and terminate in tight boxes.

N2XRY-NA2XRY
  • icona

    Vantaggi

    N2XRY/NA2XRY : Benefits and Features

  • IEC 60502-1 Compliant: Built strictly to the global standard. No shortcuts.

  • Rame o alluminio: Your call. Choose Rame for performance or Alluminio to slash the budget.

  • Steel Wire Armor (SWA): A galvanized mechanical shield. Stops the core from being crushed in rough trenches.

  • XLPE Insulation: Runs at 90 °C. Beats the old 70°C PVC limit, giving you higher efficiency.

  • Install Anywhere: Ground, ducts, or free air—the ratings cover it all.

  • 1.5mm² to 500mm²: From tiny control wires to massive feeders, we build the full range.

  • Tough PVC Jacket: Type ST1/ST2 sheath. Formulated to take a beating and keep the cable safe.

Dimensioni/Parametri

0.6/1 kV Copper Conductor XLPE Insulation Multi-core Cables Steel Wire Unarmoured Cable
Cable SectionNominal cross sectional area (mm²) / Phase ConductorMax. Conductor Resistance DC at 20 °C (Ω/km)Max. Conductor Resistance AC at 90 °C (Ω/km)Continuous Current Ratings Laid in ground (A)Continuous Current Ratings Laid in ducts (A)Continuous Current Ratings Laid in free air (A)Approx. overall diameter (mm)Approx. overall weight (kg/km)
Due cavi centrali1.512.115.428733242913.1340
Due cavi centrali2.57.419.448542313814395
Due cavi centrali44.615.878355405115.1465
Due cavi centrali63.083.927468506416.2550
Due cavi centrali101.832.333690678718.3775
Due cavi centrali161.151.46671168711420.3990
Due cavi centrali250.7270.927515111415424.11465
Due cavi centrali350.5240.668818013818826.21780
Tre cavi centrali1.512.115.428727192413.6365
Tre cavi centrali2.57.419.448535253214.6435
Tre cavi centrali44.615.878345334215.7520
Tre cavi centrali63.083.927456415317630
Tre cavi centrali101.832.333675567319.6885
Tre cavi centrali161.151.466796729621.81140
Tre cavi centrali250.7270.92751259513025.81675
Tre cavi centrali350.5240.668814210914528.21880
Tre cavi centrali500.3870.494416913217731.42385
Tre cavi centrali700.2680.343120616322236.13385
Tre cavi centrali950.1930.248124619727139.94320
Tre cavi centrali1200.1530.197627922631443.95190
Quattro cavi centrali1.512.115.428727192414.4410
Quattro cavi centrali2.57.419.448535253215.5490
Quattro cavi centrali44.615.878345334216.8600
Quattro cavi centrali63.083.927456415318955
Quattro cavi centrali101.832.333675567320.91045
Quattro cavi centrali161.151.466796729623.11490
Quattro cavi centrali250.7270.92751259513027.82025
Quattro cavi centrali350.5240.668814210914531.42370
Quattro cavi centrali500.3870.494416913217735.13000
Quattro cavi centrali700.2680.343120616322240.64285
Quattro cavi centrali950.1930.248124619727144.95410
Quattro cavi centrali1200.1530.197627922631448.87000
Quattro cavi centrali1500.1240.161231125535653.38370
Quattro cavi centrali1850.09910.130234929040758.310110
Quattro cavi centrali2400.07540.101240033647064.512720
Quattro cavi centrali3000.06010.082944637854170.615450
Quattro cavi centrali4000.0470.067649942762077.420280
Quattro cavi centrali5000.03660.056154647469585.125405
Quattro cavi centrali con neutro ridotto250.7270 / 1.15000.9275 / 1.46671259513026.91905
Quattro cavi centrali con neutro ridotto350.5240 / 1.15000.6688 / 1.466714210914528.22210
Quattro cavi centrali con neutro ridotto500.3870 / 0.72700.4944 / 0.927516913217731.92810
Quattro cavi centrali con neutro ridotto700.2680 / 0.52400.3431 / 0.6688206163222363890
Quattro cavi centrali con neutro ridotto950.1930 / 0.38700.2481 / 0.494424619727139.64925
Quattro cavi centrali con neutro ridotto1200.1530 / 0.26800.1976 / 0.343127922631442.76015
Quattro cavi centrali con neutro ridotto1500.1240 / 0.26800.1612 / 0.343131125535647.97495
Quattro cavi centrali con neutro ridotto1850.0991 / 0.19300.1302 / 0.248134929040752.89120
Quattro cavi centrali con neutro ridotto2400.0754 / 0.15300.1012 / 0.197640033647058.711375
Quattro cavi centrali con neutro ridotto3000.0601 / 0.12400.0829 / 0.161244637854163.813755
Quattro cavi centrali con neutro ridotto4000.0470 / 0.09910.0676 / 0.13024994276207317975
Quattro cavi centrali con neutro ridotto5000.0366 / 0.07540.0561 / 0.101254647469580.822485
0.6/1 kV Aluminum Conductor XLPE Insulation Multi-core Cables Steel Wire Unarmoured Cable
Cable SectionNominal cross sectional area (mm²) / Phase ConductorMax. Conductor Resistance DC at 20 °C (Ω/km)Max. Conductor Resistance AC at 90 °C (Ω/km)Continuous Current Ratings Laid in ground (A)Continuous Current Ratings Laid in ducts (A)Continuous Current Ratings Laid in free air (A)Approx. overall diameter (mm)Approx. overall weight (kg/km)
Due cavi centrali103.08003.949069516718.3660
Due cavi centrali161.91002.449090678820.3800
Due cavi centrali251.20001.53881178912023.61130
Due cavi centrali350.86801.113314010714626.21360
Tre cavi centrali103.08003.949057435619.6705
Tre cavi centrali161.91002.449074567421.8855
Tre cavi centrali251.20001.5388977410125.21195
Tre cavi centrali350.86801.11331108511325.21245
Tre cavi centrali500.64100.822413110213728.41525
Tre cavi centrali700.44300.568816012717333.12125
Tre cavi centrali950.32000.411519115321136.72585
Tre cavi centrali1200.25300.325921817624540.03005
Quattro cavi centrali103.08003.949057435620.9810
Quattro cavi centrali161.91002.449074567424.11105
Quattro cavi centrali251.20001.5388977410127.21395
Quattro cavi centrali350.86801.11331108511328.41525
Quattro cavi centrali500.64100.822413110213732.11855
Quattro cavi centrali700.44300.568816012717337.62605
Quattro cavi centrali950.32000.411519115321140.33100
Quattro cavi centrali1200.25300.325921817624545.84085
Quattro cavi centrali1500.20600.266024319927850.34770
Quattro cavi centrali1850.16400.212627422832055.35600
Quattro cavi centrali2400.12500.163431726537661.56835
Quattro cavi centrali3000.10000.132135630143067.17985
Quattro cavi centrali4000.07780.104740434650177.410730
Quattro cavi centrali5000.06050.083845239357485.112875
Quattro cavi centrali con neutro ridotto500.6410 / 1.20000.8224 / 1.538813110213731.91800
Quattro cavi centrali con neutro ridotto700.4430 / 0.86800.5688 / 1.113316012717336.02420
Quattro cavi centrali con neutro ridotto950.3200 / 0.64100.4115 / 0.822419115321139.62905
Quattro cavi centrali con neutro ridotto1200.2530 / 0.44300.3259 / 0.568821817624542.73410
Quattro cavi centrali con neutro ridotto1500.2060 / 0.44300.2660 / 0.568824319927847.94375
Quattro cavi centrali con neutro ridotto1850.1640 / 0.32000.2126 / 0.411527422832052.85160
Quattro cavi centrali con neutro ridotto2400.1250 / 0.25300.1634 / 0.325931726537658.76230
Quattro cavi centrali con neutro ridotto3000.1000 / 0.20600.1321 / 0.266035630143063.87255
Quattro cavi centrali con neutro ridotto4000.0778 / 0.16400.1047 / 0.212640434650173.09685
Quattro cavi centrali con neutro ridotto5000.0605 / 0.12500.0838 / 0.163445239357480.811615
  • icona

    Processi di produzione del cavo elettrico

Per garantire una qualità superiore, JOCA opera linee di produzione completamente digitalizzate e automatizzate per cavi alimentazione. Specificatamente, questo flusso di lavoro completo coperture trefolo conduttore, estrusione isolante, vagliatura metallica e guaina finale. Inoltre, sistemi intelligenti monitorare attivamente ogni fase per garantire prestazioni stabili e qualità del prodotto costante. In aggiunta, la fabbrica non c'è bisogno di strutture di prova avanzate, come prove di scarica parziale, prove di trazione e prove di scintilla. Di conseguenza, queste misure rigorose garanzia che ogni cavo consegnato soddisfa rigorosamente gli standard internazionali.

Processi di produzione del filo fotovoltaico

Imballaggio per la spedizione

Per soddisfare le varie esigenze di trasporto, ci sono molti metodi di imballaggio che possono essere utilizzati.

imballaggio del cavo di alimentazione

Hai altre domande?

We’ve compiled the most common questions regarding specifications, safety standards, and applications below. If you don't see what you're looking for, or have a specific custom requirement, just contact our engineering team directly.

Q: Which models are these?

A: Two main types. N2XRY uses XLPE insulation. NYRY uses PVC. If you see an ‘A’ (like NA2XRY), that just means Alluminio conductor.

 

Q: Valutazione di tensione?

 A: Bassa tensione standard: 0,6/1kV.

 

Q: Conductor materials?

 A: Your choice: Rame o Alluminio.

 

Q: What kind of armor?

A: SWA (Steel Wire Armor). Single layer of round galvanized wires. Much stronger than tape armor.

 

Q: Core configurations?

 A: We build 2, 3, and 4-core versions. We also do the 4-core with Reduced Neutral (often called 3+1).

 

Q: Jacket specs?

A: Extruded PVC. It meets IEC 60502-1 (Type ST1 or ST2). Tough enough for most sites.

 

Q: Resistance calculation temp?

A: Data is calculated at 90 °C, matching the XLPE rating.

Scorri fino in cima
Entra in contatto con la società JOCA

Compila gentilmente il modulo sottostante per contattarci. Miriamo a risponderti entro 12 ore. Ti auguro il meglio!

Contact Form Demo

JOCA