N2XSY / NA2XSY
Cable de alimentación de camisa de PVC y aislamiento XLPE único de 3,6KV-35KV
- Director:Class 2 Stranded copper/Aluminum conductor
- Conductor Screen : Semi-conductive material (Bonded Type)
- Aislamiento: XLPE(cross-linked polyethylene)
- Insulation Screen : Semi-conductive material (Strippable Type)
- Screen : Copper wires with Open Helix Copper Tape Screen
- Outer sheath : PVC (Polyinyl Chloride), black & red
- Procesamiento rápido de muestras con soluciones personalizadas
- Materiales de alta calidad
- Opciones de precios asequibles
- Entrega global
- Para una mejor protección de datos, asegúrese de que todas las cargas sean seguras
Ahorre al menos 30% en promedio
-
Descripción del producto
N2XSY / NA2XSY Power Cable : Product Description and Specifications
The N2XSY (Copper) and NA2XSY (Aluminum) series? They’re your standard workhorses for single-core Medium Voltage. We run them from 6kV up to 35kV.
Why use them? Well, we use XLPE insulation, not PE. Result? You get a 90°C rating and solid dielectric strength. And because they’re single-core, you don’t have to wrestle with them like those heavy three-core cables. They fit right into tight ducts or switchgear rooms. Basically, if you need ease of termination, this is the one.
-
Ventajas
N2XSY / NA2XSY : Benefits and Features
¿por qué XLPE? It’s simple: Low dielectric loss and a 90°C operating temp. This gives you way more thermal headroom than older PVC cables, meaning you can push higher loads safely.
Installer Friendly: The PVC jacket is formulated to be flexible. It makes wrestling the cable into tight switchgear or ducts a lot less of a headache compared to stiff PE sheaths.
Fast Jointing: We use a fully strippable semi-con screen. Your jointers will love this because they can strip it cleanly by hand without needing expensive shaving tools or risking damage to the insulation.
Safety Screen: El Pantalla de alambre de cobre (with the helix tape) isn’t just for shielding—it provides the necessary low-impedance path for earth fault currents to trip your protection gear instantly.
Dimensiones/Parámetros
| Cross sectional area (mm2) | Estructura conductora | Conductor Outer diameter (mm) | Insulation thickness (mm) | Copper tape screen (approximate) (mm) | Sheath thickness (mm) | Outer diameter (approximate) (mm) | Copper core cableweight (kg/km) | Aluminum core cableweight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 25 | Compact round | 6.0 | 2.5 | 0.12 | 1.5 | 17.2 | 510 | 354 |
| 35 | Compact round | 7.2 | 2.5 | 0.12 | 1.6 | 18.6 | 637 | 418 |
| 50 | Compact round | 8.4 | 2.5 | 0.12 | 1.6 | 19.8 | 800 | 488 |
| 70 | Compact round | 10.0 | 2.5 | 0.12 | 1.7 | 21.6 | 1029 | 591 |
| 95 | Compact round | 11.7 | 2.5 | 0.12 | 1.7 | 23.3 | 1296 | 701 |
| 120 | Compact round | 13.1 | 2.5 | 0.12 | 1.8 | 24.9 | 1566 | 815 |
| 150 | Compact round | 14.6 | 2.5 | 0.12 | 1.8 | 26.4 | 1873 | 934 |
| 185 | Compact round | 16.3 | 2.5 | 0.12 | 1.9 | 28.3 | 2244 | 1085 |
| 240 | Compact round | 18.5 | 2.6 | 0.12 | 1.9 | 30.7 | 2805 | 1302 |
| 300 | Compact round | 20.7 | 2.8 | 0.12 | 2.0 | 33.7 | 3456 | 1576 |
| 400 | Compact round | 23.8 | 3.0 | 0.12 | 2.2 | 37.4 | 4501 | 1994 |
| 500 | Compact round | 26.6 | 3.2 | 0.12 | 2.3 | 41.4 | 5546 | 2412 |
| 630 | Compact round | 30.1 | 3.2 | 0.12 | 2.4 | 45.1 | 6853 | 2905 |
| 800 | Compact round | 35.0 | 3.2 | 0.12 | 2.5 | 50.4 | 8576 | 3562 |
| 1000 | Milliken conductor | 39.5 | 3.2 | 0.12 | 2.6 | 55.3 | 10592 | 4306 |
| Cross sectional area (mm2) | Estructura conductora | Conductor Outer diameter (mm) | Insulation thickness (mm) | Copper tape screen (approximate) (mm) | Sheath thickness (mm) | Outer diameter (approximate) (mm) | Copper core cableweight (kg/km) | Aluminum core cable weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 25 | Compact round | 6.0 | 3.4 | 0.12 | 1.6 | 19.4 | 580 | 423 |
| 35 | Compact round | 7.2 | 3.4 | 0.12 | 1.6 | 20.6 | 702 | 483 |
| 50 | Compact round | 8.4 | 3.4 | 0.12 | 1.7 | 22.0 | 878 | 566 |
| 70 | Compact round | 10.0 | 3.4 | 0.12 | 1.7 | 23.6 | 1103 | 665 |
| 95 | Compact round | 11.7 | 3.4 | 0.12 | 1.8 | 25.5 | 1386 | 791 |
| 120 | Compact round | 13.1 | 3.4 | 0.12 | 1.8 | 26.9 | 1649 | 898 |
| 150 | Compact round | 14.6 | 3.4 | 0.12 | 1.9 | 28.6 | 1974 | 1035 |
| 185 | Compact round | 16.3 | 3.4 | 0.12 | 1.9 | 30.3 | 2337 | 1178 |
| 240 | Compact round | 18.5 | 3.4 | 0.12 | 2.0 | 32.7 | 2908 | 1406 |
| 300 | Compact round | 20.7 | 3.4 | 0.12 | 2.1 | 35.3 | 3544 | 1664 |
| 400 | Compact round | 23.8 | 3.4 | 0.12 | 2.2 | 38.6 | 4554 | 2047 |
| 500 | Compact round | 26.6 | 3.4 | 0.12 | 2.3 | 42.2 | 5574 | 2440 |
| 630 | Compact round | 30.1 | 3.4 | 0.12 | 2.4 | 45.9 | 6884 | 2936 |
| 800 | Compact round | 35.0 | 3.4 | 0.12 | 2.5 | 51.2 | 8611 | 3597 |
| 1000 | Milliken conductor | 39.5 | 3.4 | 0.12 | 2.7 | 56.3 | 10655 | 4369 |
| Conductor Cross sectional area (mm2) | Estructura conductora | Conductor Outer diameter (mm) | Insulation thickness (mm) | Copper tape screen (approximate) (mm) | Sheath thickness (mm) | Outer diameter (approximate) (mm) | Copper core cable weight (kg/km) | Aluminum core cable weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 35 | Compact round | 7.2 | 5.5 | 0.12 | 1.8 | 25.2 | 896 | 677 |
| 50 | Compact round | 8.4 | 5.5 | 0.12 | 1.8 | 26.4 | 1071 | 759 |
| 70 | Compact round | 10.0 | 5.5 | 0.12 | 1.9 | 28.2 | 1320 | 882 |
| 95 | Compact round | 11.7 | 5.5 | 0.12 | 1.9 | 29.9 | 1604 | 1009 |
| 120 | Compact round | 13.1 | 5.5 | 0.12 | 2.0 | 31.5 | 1892 | 1141 |
| 150 | Compact round | 14.6 | 5.5 | 0.12 | 2.0 | 33.0 | 2215 | 1275 |
| 185 | Compact round | 16.3 | 5.5 | 0.12 | 2.1 | 34.9 | 2605 | 1447 |
| 240 | Compact round | 18.5 | 5.5 | 0.12 | 2.2 | 37.3 | 3196 | 1693 |
| 300 | Compact round | 20.7 | 5.5 | 0.12 | 2.2 | 39.7 | 3833 | 1953 |
| 400 | Compact round | 23.8 | 5.5 | 0.12 | 2.3 | 43.0 | 4867 | 2360 |
| 500 | Compact round | 26.6 | 5.5 | 0.12 | 2.4 | 46.6 | 5902 | 2769 |
| 630 | Compact round | 30.1 | 5.5 | 0.12 | 2.5 | 50.3 | 7250 | 3302 |
| 800 | Compact round | 35.0 | 5.5 | 0.12 | 2.7 | 55.8 | 9040 | 4026 |
| 1000 | Milliken conductor | 39.5 | 5.5 | 0.12 | 2.8 | 60.7 | 11096 | 4810 |
| Conductor Cross sectional area (mm2) | Estructura conductora | Conductor Outer diameter (mm) | Insulation thickness (mm) | Copper tape screen (approximate) (mm) | Sheath thickness (mm) | Outer diameter (approximate) (mm) | Copper core cable weight (kg/km) | Aluminum core cable weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 50 | Compact round | 8.4 | 8.0 | 0.12 | 2.0 | 31.8 | 1354 | 1042 |
| 70 | Compact round | 10.0 | 8.0 | 0.12 | 2.0 | 33.4 | 1604 | 1166 |
| 95 | Compact round | 11.7 | 8.0 | 0.12 | 2.1 | 35.3 | 1918 | 1323 |
| 120 | Compact round | 13.1 | 8.0 | 0.12 | 2.1 | 36.7 | 2204 | 1453 |
| 150 | Compact round | 14.6 | 8.0 | 0.12 | 2.2 | 38.4 | 2557 | 1617 |
| 185 | Compact round | 16.3 | 8.0 | 0.12 | 2.2 | 40.1 | 2946 | 1788 |
| 240 | Compact round | 18.5 | 8.0 | 0.12 | 2.3 | 42.5 | 3557 | 2055 |
| 300 | Compact round | 20.7 | 8.0 | 0.12 | 2.4 | 45.1 | 4236 | 2355 |
| 400 | Compact round | 23.8 | 8.0 | 0.12 | 2.5 | 48.4 | 5299 | 2792 |
| 500 | Compact round | 26.6 | 8.0 | 0.12 | 2.6 | 52.0 | 6354 | 3220 |
| 630 | Compact round | 30.1 | 8.0 | 0.12 | 2.7 | 55.7 | 7748 | 3799 |
| 800 | Compact round | 35.0 | 8.0 | 0.12 | 2.8 | 61.0 | 9560 | 4546 |
| 1000 | Milliken conductor | 39.5 | 8.0 | 0.12 | 3.0 | 66.1 | 11687 | 5401 |
| Conductor Cross sectional area (mm2) | Estructura conductora | Conductor Outer diameter (mm) | Insulation thickness (mm) | Copper tape screen (approximate) (mm) | Sheath thickness (mm) | Outer diameter (approximate) (mm) | Copper core cable weight (kg/km) | Aluminum core cable weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 50 | Compact round | 8.4 | 9.3 | 0.12 | 2.1 | 34.8 | 1533 | 1221 |
| 70 | Compact round | 10.0 | 9.3 | 0.12 | 2.1 | 36.4 | 1791 | 1353 |
| 95 | Compact round | 11.7 | 9.3 | 0.12 | 2.2 | 38.3 | 2115 | 1520 |
| 120 | Compact round | 13.1 | 9.3 | 0.12 | 2.2 | 39.7 | 2408 | 1656 |
| 150 | Compact round | 14.6 | 9.3 | 0.12 | 2.3 | 41.4 | 2769 | 1830 |
| 185 | Compact round | 16.3 | 9.3 | 0.12 | 2.3 | 43.1 | 3167 | 2009 |
| 240 | Compact round | 18.5 | 9.3 | 0.12 | 2.4 | 45.5 | 3790 | 2287 |
| 300 | Compact round | 20.7 | 9.3 | 0.12 | 2.5 | 48.1 | 4481 | 2601 |
| 400 | Compact round | 23.8 | 9.3 | 0.12 | 2.6 | 51.4 | 5561 | 3054 |
| 500 | Compact round | 26.6 | 9.3 | 0.12 | 2.7 | 57.1 | 6894 | 3760 |
| 630 | Compact round | 30.1 | 9.3 | 0.12 | 2.8 | 60.8 | 8263 | 4314 |
| 800 | Compact round | 35.0 | 9.3 | 0.12 | 3.0 | 66.3 | 10257 | 5243 |
| 1000 | Milliken conductor | 39.5 | 9.3 | 0.12 | 3.1 | 71.2 | 12369 | 6083 |
| Conductor Cross sectional area (mm2) | Estructura conductora | Conductor Outer diameter (mm) | Insulation thickness (mm) | Copper tape screen (approximate) (mm) | Sheath thickness (mm) | Cable Outer diameter (approximate) (mm) | Copper core cableweight (kg/km) | Aluminum core cable weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 50 | Compact round | 8.4 | 10.5 | 0.12 | 2.2 | 37.6 | 1715 | 1402 |
| 70 | Compact round | 10.0 | 10.5 | 0.12 | 2.2 | 39.2 | 1980 | 1541 |
| 95 | Compact round | 11.7 | 10.5 | 0.12 | 2.3 | 41.1 | 2313 | 1718 |
| 120 | Compact round | 13.1 | 10.5 | 0.12 | 2.3 | 42.5 | 2612 | 1860 |
| 150 | Compact round | 14.6 | 10.5 | 0.12 | 2.4 | 44.2 | 2981 | 2042 |
| 185 | Compact round | 16.3 | 10.5 | 0.12 | 2.4 | 45.9 | 3387 | 2229 |
| 240 | Compact round | 18.5 | 10.5 | 0.12 | 2.5 | 48.3 | 4021 | 2519 |
| 300 | Compact round | 20.7 | 10.5 | 0.12 | 2.6 | 50.9 | 4725 | 2845 |
| 400 | Compact round | 23.8 | 10.5 | 0.12 | 2.7 | 54.2 | 5820 | 3313 |
| 500 | Compact round | 26.6 | 10.5 | 0.12 | 2.8 | 59.7 | 7142 | 4009 |
| 630 | Compact round | 30.1 | 10.5 | 0.12 | 2.9 | 63.4 | 8528 | 4579 |
| 800 | Compact round | 35.0 | 10.5 | 0.12 | 3.1 | 68.7 | 10521 | 5507 |
| 1000 | Milliken conductor | 39.5 | 10.5 | 0.12 | 3.2 | 73.6 | 12652 | 6366 |
-
Procesos de producción de cables de alimentación
Para garantizar una calidad superior, JOCA opera líneas de producción totalmente digitalizadas y automatizadas para cables de alimentación. Específicamente, este flujo de trabajo integral cubiertas trenzado de conductores, extrusión aislante, cribado metálico y revestimiento final. Además, sistem intelligent monitorear activamente cada etapa para garantizar un rendimiento estable y una calidad constante del producto. Además, la fábrica utiliza instalaciones de prueba avanzadas, como pruebas de descarga parcial, pruebas de tracción y pruebas de chispas. En consecuencia, estas medidas rigurosas garantía que cada cable entregado cumpla estrictamente con los estándares internacionales.
Embalaje para envío
Para satisfacer diversas necesidades de transporte, existen muchos métodos de embalaje que se pueden utilizar.
¿Tienes más preguntas?
Q: N2XSY vs. NA2XSY: What’s the difference?
A: Sólo el metal conductor. N2XSY es cobre. NA2XSY (with the ‘A’) is Aluminum. That’s it. Aluminum is way cheaper and lighter, while Copper carries more load.
Q: What voltage does this cover?
A: The whole Medium Voltage range. Starts at 3.6kV, goes right up to 35kV.
Q: What’s the sheath material?
A: Estándar PVC. It’s flexible, which saves you a lot of trouble when pulling it through indoor conduits or tight trays.
Q: Can I bury this directly in the ground?
A: Technically, yes, if it’s dry. But honestly? For direct burial, you really should ask for the PE sheath version (N2XS2Y). It handles wet soil way better than PVC. Don’t risk it if the ground is swampy.
Q: What colors do you have?
A: Mostly Rojo o Negro. Need something else? We can run a custom batch for you, just ask.
Q: Is the insulation screen strippable?
A: Fully Strippable. Your jointers will thank you. It peels off clean by hand—no need for those expensive shaving tools.
Q: Can I get a sample?
A: Sí. We can ship a short cut so you can inspect the layers and quality yourself before buying a full drum.
Q: Is the conductor solid or stranded?
A: Class 2 Stranded (Compacted). It keeps the cable diameter tight but still flexible enough to handle.