JOCA

N2XSEY/NA2XSEY

3.6KV-35KV Multi XLPE Insulation and PVC Jacket power cable

  • Rated Voltage: 3.6/6kV to 26/35kV

  • Conductor: Stranded Compacted Copper (N2XSEY) or Aluminium (NA2XSEY) – Class 2

  • Conductor Screen: Extruded Semi-conductive Compound

  • Insulation: Cross-linked Polyethylene (XLPE)

  • Insulation Screen: Extruded Semi-conductive Compound

  • Metallic Screen: Copper Tape or Copper Wire Screen

  • Bedding / Inner Covering: PVC or PP Filler

  • Outer Sheath: PVC (Polyvinyl Chloride), Red or Black

  • Max. Operating Temperature: 90°C

 Save at least 30% on average

N2XSEY
  • icon

    Product Description

    N2XSEY/NA2XSEY​ : Product Description and Specifications

The N2XSY (Copper) and NA2XSY (Aluminum) series are your go-to cables for the Medium Voltage (MV) grid—anything from 3.6kV up to 35kV. Here’s the critical part: Since it’s MV, we wrap the XLPE insulation with a Copper Wire Screen. This isn’t optional—it manages the electric field stress and handles fault currents to keep the system safe. Your choice: Need standard protection? Stick with the PVC sheath. Running it in wet ground? Upgrade to PE (Polyethylene) to seal out moisture completely.

N2XSEY_1
  • icon

    Advantages

    N2XSEY/NA2XSEY​ : Benefits and Features

  • 6/10kV Ready: Built strictly to VDE and IEC standards. No guessing.

  • Copper or Aluminum: Your call. Go Copper for performance or Aluminum to save the budget.

  • Real Screening: Copper wire screen + semi-con layers. Essential for managing electric field stress (so it doesn’t fail).

  • XLPE Insulation: Tough stuff. Survives 250°C short circuit spikes without melting.

  • Install Anywhere: Underground, ducts, or outdoors. The PVC/PE sheath takes the beating.

  • Safety First: The copper screen ensures you have solid earthing protection.

Dimensions/Parameters

3.6/6 (7.2) KV XLPE/PVC 3 cores (non-armored) YJV, YJLV
Cross sectional area (mm2)Conductor StructureConductor Outer diameter (mm)Insulation thickness (mm)Copper tape screen (approximate) (mm)Sheath thickness (mm)Outer diameter (approximate) (mm)Copper core cableweight (kg/km)Aluminum core cableweight (kg/km)
25Compact round6.02.50.122.134.715211049
35Compact round7.22.50.122.237.518911230
50Compact round8.42.50.122.340.224021458
70Compact round10.02.50.122.443.930821760
95Compact round11.72.50.122.547.839142121
120Compact round13.12.50.122.651.147222456
150Compact round14.62.50.122.754.556762844
185Compact round16.32.50.122.858.467863293
240Compact round18.52.60.123.063.985354004
300Compact round20.72.80.123.270.3105124849
400Compact round23.83.00.123.578.4136646113
500Compact round26.63.20.123.787.0169187479
6 (7.2), 6/10 (12) KV XLPE/PVC 3 cores (non-armored) YJV, YJLV
Cross sectional area (mm2)Conductor StructureConductor Outer diameter (mm)Insulation thickness (mm)Copper tape screen (approximate) (mm)Sheath thickness (mm)Outer diameter (approximate) (mm)Copper core cableweight (kg/km)Aluminum core cable weight (kg/km)
25Compact round6.03.40.122.238.917281256
35Compact round7.23.40.122.341.621111451
50Compact round8.43.40.122.444.426361692
70Compact round10.03.40.122.548.133362015
95Compact round11.73.40.122.752.041852392
120Compact round13.13.40.122.855.250092743
150Compact round14.63.40.122.958.759793148
185Compact round16.33.40.123.062.571093616
240Compact round18.53.40.123.167.688454314
300Compact round20.73.40.123.373.1107645101
400Compact round23.83.40.123.580.2138486297
500Compact round26.63.40.123.787.9170197580
8.7/10 (12), 8.7/15 (17.5) KV XLPE/PVC 3 cores (non-armored) YJV, YJLV
Cross sectional area (mm2)StructureOuter diameter (mm)Insulation thickness (mm)Copper tape screen (approximate) (mm)Sheath thickness (mm)Outer diameter (approximate) (mm)Copper core cableweight (kg/km)Aluminum core cable weight (kg/km)
25Compact round6.04.50.122.443.920081536
35Compact round7.24.50.122.546.724111750
50Compact round8.44.50.122.649.529532009
70Compact round10.04.50.122.753.236722351
95Compact round11.74.50.122.857.145442751
120Compact round13.14.50.122.960.353873122
150Compact round14.64.50.123.063.763783546
185Compact round16.34.50.123.167.675314038
240Compact round18.54.50.123.372.792974767
300Compact round20.74.50.123.578.2112495586
400Compact round23.84.50.123.785.3143766825
500Compact round26.64.50.123.993.0175928153
12/20 (24) XLPE/PVC 3 cores (non-armored) YJV, YJLV
Conductor Cross sectional area (mm2)Conductor StructureConductor Outer diameter (mm)Insulation thickness (mm)Copper tape screen (approximate) (mm)Sheath thickness (mm)Outer diameter (approximate) (mm)Copper core cable weight (kg/km)Aluminum core cable weight (kg/km)
35Compact round7.25.50.122.651.327082047
50Compact round8.45.50.122.754.132642320
70Compact round10.05.50.122.857.840042682
95Compact round11.75.50.123.061.748973103
120Compact round13.15.50.123.164.957573492
150Compact round14.65.50.123.268.367673935
185Compact round16.35.50.123.372.279414448
240Compact round18.55.50.123.577.397355204
300Compact round20.75.50.123.682.8117166053
400Compact round23.85.50.123.889.9148827331
500Compact round26.65.50.124.097.6181408701
18/30 (36) XLPE/PVC 3 cores (non-armored) YJV, YJLV
Conductor Cross sectional area (mm2)Conductor StructureConductor Outer diameter (mm)Insulation thickness (mm)Copper tape screen (approximate) (mm)Sheath thickness (mm)Outer diameter (approximate) (mm)Copper core cable weight (kg/km)Aluminum core cable weight (kg/km)
50Compact round8.48.00.123.165.641543210
70Compact round10.08.00.123.269.349423621
95Compact round11.78.00.123.373.258894095
120Compact round13.18.00.123.576.467934527
150Compact round14.68.00.123.679.978495018
185Compact round16.38.00.123.783.890755583
240Compact round18.58.00.123.888.8109396408
300Compact round20.78.00.124.094.3129947330
400Compact round23.88.00.124.2101.4162578706
500Compact round26.68.00.124.4109.21961910180
21/35 (40.5) XLPE/PVC 3 cores (non-armored) YJV, YJLV
Conductor Cross sectional area (mm2)Conductor StructureConductor Outer diameter (mm)Insulation thickness (mm)Copper tape screen (approximate) (mm)PVC bedding thickness (mm)Armored tape outer diameter (mm)Sheath thickness (mm)Outer diameter (approximate) (mm)Copper core cable weight (kg/km)Aluminum core cable weight (kg/km)
25Compact round6.04.50.11.40.52.548.932272755
35Compact round7.24.50.11.40.52.651.737113050
50Compact round8.44.50.11.50.52.754.743723428
70Compact round10.04.50.11.50.52.858.452083886
95Compact round11.74.50.11.60.53.062.662714477
120Compact round13.14.50.11.70.53.166.072544989
150Compact round14.64.50.11.70.53.269.584205588
185Compact round16.34.50.11.80.53.373.597316239
240Compact round18.54.50.11.90.53.578.9117157184
300Compact round20.74.50.12.00.83.785.8147749111
400Compact round23.84.50.12.10.83.993.11835010798
500Compact round26.64.50.12.20.84.1101.02199012551
26/35 (40.5) XLPE/PVC 3 cores (non-armored) YJV, YJLV
Conductor Cross sectional area (mm2)Conductor StructureConductor Outer diameter (mm)Insulation thickness (mm)Copper tape screen (approximate) (mm)Sheath thickness (mm)Cable Outer diameter (approximate) (mm)Copper core cableweight (kg/km)Aluminum core cable weight (kg/km)
50Compact round8.410.50.13.578.052894345
70Compact round10.010.50.13.681.761314809
95Compact round11.710.50.13.785.671345341
120Compact round13.110.50.13.888.880865821
150Compact round14.610.50.13.992.391936361
185Compact round16.310.50.14.196.1104766983
240Compact round18.510.50.14.2101.2124147883
300Compact round20.710.50.14.4106.7145488885
400Compact round23.810.50.14.6113.81791710365
  • icon

    Production Processes Of Power cable

To ensure superior quality, JOCA operates fully digitalized and automated production lines for power cables. Specifically, this comprehensive workflow covers conductor stranding, insulation extrusion, metallic screening, and final sheathing. Moreover, intelligent systems actively monitor each stage to ensure stable performance and consistent product quality. In addition, the factory utilizes advanced testing facilities, such as partial discharge testing, tensile testing, and spark testing. Consequently, these rigorous measures guarantee that every delivered cable strictly meets international standards.

Packing For Shipment

To meet various transportation needs, there are many methods of packaging that can be used.

power cable packing

Have more questions?

Easily get started by finding the answers to commonly asked questions about our company and services.

Q: What does "N2XSEY" actually mean?

 A: It’s just VDE shorthand. Here’s the cheat sheet:

  • 2X = XLPE Insulation.

     
  • S = Copper Screen (Crucial for MV).

  • Y = PVC Jacket.

     
  • E = Bedding layer.

Q: N2XSEY vs. NA2XSEY: The difference?

A: Simple. N2XSEY is Copper. NA2XSEY (with the ‘A’) is Aluminum. Copper carries more current; Aluminum saves you money.

 

Q: Why use XLPE instead of PVC insulation?

A: Heat tolerance. PVC quits at 70°C. XLPE runs happily at 90°C. That extra headroom means you can push significantly more power through the line without melting it.

 

Q: Why does it need those screens?

A: To stop it from blowing up. The semi-con layers keep the electric field smooth so the insulation doesn’t fail. The Copper Screen? That’s your safety path for earth faults. Don’t run MV without it.

 

Q: Where can I install this?

A: Indoors, ducts, or underground—it’s versatile. But be careful: It has no armor. If you bury it directly, lay it in soft sand. Don’t let rocks crush it.

 

Q: What standards do you follow?

A: We don’t mess around with high voltage. It’s built strictly to IEC 60502-2 and VDE 0276-620.

 

Q: How tight can I bend it?

A: 15x the Diameter. Respect that number. If you force a tighter bend, you’ll crack the screen or the insulation, and the cable will fail.

 

Q: Can I get a different color?

A: Sure. Red is standard, but if you need Black or Flame Retardant (FR) PVC for a specific project, just tell us. We’ll extrude it to order.